SF₆-Free Medium-Voltage Switchgear

Voltberg SF₆-Free Medium-Voltage Switchgear

SF₆-free technology, two distinct product groups and application-specific switching options.

The Voltberg SF₆-Free product family comprises two distinct product groups for different medium-voltage switching and protection requirements: vacuum circuit-breaker panels with air-insulated disconnectors and vacuum-interrupter load-break switch panels.

Check Out The Catalogue

1. Vacuum Circuit-Breaker Panels with AIS Disconnectors

In this product group, current interruption is performed by a vacuum circuit breaker, while isolation is provided by an air-insulated disconnector. The circuit breaker and disconnector are separate devices with distinct functions.

The Voltberg VCB and Thytronic XMR-P protection relay solution is configured according to the feeder’s switching, protection and control requirements. ABB or Siemens vacuum circuit-breaker options may also be evaluated according to project specifications.

Typical applications

  • Circuit-breaker incoming and outgoing feeders
  • Transformer protection
  • Bus coupling
  • Distribution and industrial applications requiring relay-based protection

2. Vacuum-Interrupter Load-Break Switch Panels

In this product group, load-current switching is performed by a load-break switch incorporating a VI (Vacuum Interrupter). Two separate options are available:

Load-Break Switch Panel

Used to make and break normal load current. It provides a switching solution for incoming, outgoing and ring-network applications.

Load-Break Switch Panel with Fuses

Combines a vacuum-interrupter load-break switch with medium-voltage fuses. In transformer applications, the load-break switch performs load switching, while correctly selected fuses provide short-circuit protection. Fuse selection and tripping coordination are defined according to the transformer characteristics.

Product Selection for Your Project

Circuit-breaker and load-break switch product groups are selected separately according to the application’s switching and protection requirements. Voltage level, rated current, short-circuit ratings, interlocks and type-test coverage are specified in the technical documentation for the offered configuration.

Let us select the right SF₆-Free panel for your project.

Contact Voltberg for technical information and a quotation.

Get a Quote

SF₆-Free Medium-Voltage Switchgear (VB Series SF₆-Free)

Voltberg VB series SF₆-free switchgear is a medium-voltage switching solution that does not use SF₆ gas, developed for modern electricity distribution networks and a greener future. Solid and dry-air insulation is used instead of SF₆ gas, which has a global warming potential thousands of times higher than carbon dioxide. This delivers the same electrical performance as SF₆ switchgear while removing environmental obligations such as gas management and leakage monitoring.

Why SF₆-free?

The European Union’s F-gas Regulation 2024/573 progressively bans the use of F-gases in new MV switchgear: from 2026 for equipment up to 24 kV, and from 2030 for equipment between 24 and 52 kV (with certain exceptions). In projects aimed at the EU market, in renewable energy investments and in organisations with sustainability targets, SF₆-free switchgear is rapidly becoming the standard.

Key features

  • SF₆-free insulation technology (solid and dry air)
  • Vacuum interruption technology
  • Compact modular design
  • Low maintenance requirement; no gas pressure monitoring needed
  • Suitable for renewable energy and modern distribution networks
  • 24 / 48 / 110 VDC auxiliary voltage (optional)

Technical specifications

ParameterValue
Rated voltage12 / 24 / 36 kV
Rated currentUp to 1250 A
Short-circuit breaking capacityUp to 25 kA
InsulationSolid and dry air (SF₆-free)
Interrupting mediumVacuum
Auxiliary voltage24 / 48 / 110 VDC (optional)
StandardIEC 62271-200

Vacuum circuit-breaker module (side-mounted mechanism)

In the vacuum switching module marked ECO, used throughout the SF₆-free series, the operating mechanism is located at the side of the panel rather than at the front. Opening and closing are performed with a long-lever handle; spring charging is motor-operated and a separate earthing switch is located underneath. Thanks to local closing and opening buttons, a position indicator and a manual spring-charging lever, the circuit breaker can also be operated without external energy. The front face has an operations counter and a spring status indicator.

ParameterValue
Type (example)VB-24VCI24-EK0
Rated voltage (Ur)12 / 24 / 36 kV
Rated current (Ir)1250 A
Short-circuit breaking current (Isc)25 kA
Lightning impulse withstand voltage125 kV (24 kV example)
Control voltageAC 220 V
StandardIEC 62271-100

Quality and testing

Every SF₆-free switchgear unit leaving our Sincan facility carries its own nameplate showing the rated voltage, rated current, short-circuit breaking capacity and the relevant IEC standard, and undergoes routine testing before shipment. The insulation performance of each production batch is verified on a dielectric withstand test bench.

TEDAŞ approval

Voltberg kiosks and MV switchgear are type-tested, TEDAŞ-approved and approved by all electricity distribution companies in Türkiye. Type tests have been carried out at independent, internationally accredited laboratories (LVT Test Laboratories – Türkiye, KEMA Labs – the Netherlands, ICMET Craiova – Romania). Test reports and certificates are shared on request for tender and project files.

Frequently Asked Questions

Does SF₆-free switchgear perform as well as SF₆ switchgear?

Yes. VB series SF₆-free switchgear offers the same electrical performance as the SF₆ version, up to values of 12/24/36 kV, 1250 A and 25 kA.

Can SF₆-free switchgear be exported to the EU?

Considering the restrictions the EU F-gas Regulation places on new MV switchgear, SF₆-free technology is a suitable solution for projects aimed at the EU market. The grid specification of the country concerned should be confirmed separately on a project basis.

How is SF₆-free switchgear maintained?

Maintenance requirements are low because no gas pressure monitoring or gas refilling is needed.

For a configuration and price quotation suited to your project, send us your single-line diagram or equipment list; our engineering team will prepare a tailored solution for you. Get a quote →

📄 Download the e-catalogue (PDF)